The catalogue figure for a vacuum insulation panel (VIP) is the centre-of-panel value measured just after production. The number to use in the field is about double: gas and moisture entering through the barrier over time and the thermal bridge at the edge raise conductivity.

Conditionλ, W/(m·K)
VIP, after production0.004-0.0048
VIP, including 25 years and edge effect0.007-0.008
Punctured VIP0.020-0.023
Aerogel, 20 °C0.014-0.020

Edge and size. IEA Annex 39 recommends panels of at least 0.5 m x 0.5 m and close to square: because the foil conducts heat at the edge, many small panels do worse than a few large ones. A VIP cannot be cut on site, so the layout is drawn up in advance.

Damage and aerogel

In a punctured panel the vacuum is lost and conductivity rises about fivefold. Aerogel is insensitive to puncture and can be cut, but it is not as thin as a VIP. When buying, ask whether the figure includes ageing and edge, and how a puncture would be noticed.