The catalogue figure for a vacuum insulation panel (VIP) is the centre-of-panel value measured just after production. The number to use in the field is about double: gas and moisture entering through the barrier over time and the thermal bridge at the edge raise conductivity.
| Condition | λ, W/(m·K) |
|---|---|
| VIP, after production | 0.004-0.0048 |
| VIP, including 25 years and edge effect | 0.007-0.008 |
| Punctured VIP | 0.020-0.023 |
| Aerogel, 20 °C | 0.014-0.020 |
Edge and size. IEA Annex 39 recommends panels of at least 0.5 m x 0.5 m and close to square: because the foil conducts heat at the edge, many small panels do worse than a few large ones. A VIP cannot be cut on site, so the layout is drawn up in advance.
Damage and aerogel
In a punctured panel the vacuum is lost and conductivity rises about fivefold. Aerogel is insensitive to puncture and can be cut, but it is not as thin as a VIP. When buying, ask whether the figure includes ageing and edge, and how a puncture would be noticed.