The heat entering a box is the product of three values: Q = K × S × ΔT. K is the heat transfer coefficient of the insulation (W/m²K), S the surface of the box (m²), ΔT the difference between the outside and the internal target. The result comes out in watts.
In ATP, S is the geometric mean of the inside and outside surface areas of the box. The K from the box's report is used; the class limit is the upper value: 0.70 for a normally insulated (IN) box and 0.40 W/m²K for a heavily insulated (IR) one.
| Input | Example |
|---|---|
| K (IR upper limit) | 0.40 W/m²K |
| S | 5 m² |
| ΔT (30 °C outside, 5 °C inside) | 25 K |
| Heat gain | 0.40 × 5 × 25 = 50 W |
50 W is 180 kJ per hour (W × 3600 s). The sum does not see door openings, the thermal mass of the load, a surface heating in the sun or wind; it gives an order of magnitude, and plate count and duration are confirmed by measurement. Use the hottest day for the outside temperature, because an average does not hold at noon.