GEBHARDT requires the filling of a eutectic plate to be fully frozen and solid before use. The plate is frozen at least 5 °C below its melting point; the recommended time is 24 hours, and depending on the cooling technology it can run anywhere from 8 to 24 hours.
| Melting point | Freezing temperature |
|---|---|
| -3 °C | -8 °C |
| -14 °C | -19 °C |
| -18 °C | -23 °C |
| -21 °C | -26 °C |
While freezing, the plates must not touch each other; a gap has to remain so cold air can circulate between them, and GEBHARDT recommends its freezing rack for this.
At take-out, tilt the plate. If liquid slides inside, the filling has not solidified and the plate stays out of dispatch. If nothing moves the filling is solid, but a shake does not show that the temperature reached 5 °C below the melting point; the measured cabinet temperature and the plate's in and out times prove that.